15.4 Error monitoring

Detected errors are displayed on the SCB as shown in Figure 23.
Table 3 lists all error numbers with corresponding possible solutions.
No.
Cause
Er01
Input pair
I11-I21 / I12-I22:
Difference time is exceeded
or single channel is switched
off and switched-on again
Hung reset button. Input X1 (if
Er11
manual, monitored resetis
configured)
Er17
PUK Incorrect
Er18
PIN Incorrect
Er49
Waiting state for the transition
into an error mode (e.g. on
expiry of a configured delay
time)
Er51
Fault on Input circuit
channel 1
Er52
Fault on Input circuit
channel 2
Er68
Varaints SCB-03 / SCB-04:
Failure at O1 or O2. Or
internal failure
Er69
Variant SCB-02:
Er70
Internal failure
Er91
Internal device fault
to
Er99
H. ZANDER GmbH & Co. KG • Am Gut Wolf 15 • 52070 Aachen • Deutschland • Tel +49 241 9105010
Fax +49 241 91050138 • info@zander-aachen.de • www.zander-aachen.de
Y1
Y1
Figure 23: Error number on display
Solution / Acknowledgement
Check wiring
Check the function of the connected sensor
Acknowledgement by opening and closing the safety circuit within
the difference time (3 s)
Choose configuration with manual reset, but wired as autom.reset
Check wiring
Check the function of the start button
Acknowledgement by switching off and again switching on the
reset button
Acknowledgement by pressing the button for 2 seconds
Acknowledgement by pressing the button for 2 seconds
Wait for the original fault number
Check wiring for cross circuits and short circuits
Check assignment: I21 → I11; I22 → I12
Acknowledgement by pressing the button
Check wiring for cross circuits and short circuits
Check capacity an the output (see tech. data)
If applicable, internal device error. Contact the Support of the
manufacturer
Check the safety outputs for cross circuits and short circuits and
restart the device.
If the problem continues:
Reset the device to factory defaults
If the problem continues:
Contact the support of the manufacturer
Table 3: Error number list