As-i modul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

LED red (FAULT) flashing:
* The LED state reflects the status of the voltage from which the sen-
sor is supplied, i.e. it depends on the selected link position.
**Periphery fault
A periphery fault is indicated if at least one of the signals analogue
1 or analogue 2 is outside the value range or nothing is connected
to at least one analogue channel.
Measuring range of the analogue input modules:
For the measuring ranges, the LED states and their meaning please see
the following tables:
Analogue input module 2I, 4...20 mA - AC2616
Range
4 ... 20 mA
< 1 mA
1 mA ...
3.999 mA
4 mA ... 20 mA
20.001 mA ...
23 mA
> 23 mA
14
Units
dec.
32767
1000 ... 3999
4000 ... 20000
20001 ... 23000
32767
periphery fault**
Units
hex.
7FFF
03E8 ... 0F9F
0FA0 ... 4E20
4E21 ... 59D8
7FFF
LED
Meaning
analog
out
wire break
on
below nominal
on
nominal range
on
above nominal
flashes
outside range
range
range