Herunterladen Inhalt Inhalt Diese Seite drucken

IFM Electronic AC2616 Montageanleitung Seite 11

As-i modul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Electrical connection
Connection of a 2-wire sensor
analogue module 2-wire sensor
I+
C1/2 (AC2616)
V1/2 (AC2617)
COM1/2
I-
Connection of a 3-wire sensor
analogue module 3-wire sensor
I+
C1/2 (AC2616)
V1/2 (AC2617)
COM1/2
I-
Connection of a 4-wire sensor
analogue module 4-wire sensor
I+
C1/2 (AC2616)
V1/2 (AC2617)
COM1/2
I-
A 2-wire sensor is connected via the
terminals I+ and C1/2 (AC2616) or
+
V1/2 (AC2617).
-
The terminals I- and COM1/2 must
be connected to each other via a
link.
A 3-wire sensor is connected via the
terminals I+, I- and C1/2 (AC2616)
U+
or V1/2 (AC2617).
The terminals I- and COM1/2 must
I/U
be connected to each other via a
U-
link.
A 4-wire sensor is connected via the
terminals I+, I- and C1/2 (AC2616)
or V1/2 (AC2617) and COM1/2.
U+
I/U+
I/U-
U-
11

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ac2617

Inhaltsverzeichnis