Herunterladen Inhalt Inhalt Diese Seite drucken

Carrier 10TE Serie Installations-, Betriebs- Und Wartungsanweisungen Seite 21

Plattenwärmetauscher und dichtungen
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 98
required, please note that the heat exchangers should never
be tested at pressures greater than the test pressure (PT)
specified on the data plate and that the pressure differen-
ces between the two circuits during testing should never be
Product picture - black and white
higher than the maximum allowable differential pressure.
with Carrier logo on it
• If a leak occurs, lower the pressure then retighten the nuts
and repeat the test. If the leak persists, check the gaskets
and plates for signs of wear, damage or dirt. If necessary,
replace the gaskets.
5.9 - Plate codes
Example with balanced H and L patterns
N.
Tipo
7
K1234H
1
K1234H*
8
Z1234L
2
Z1234L
9
K1234H
3
K1234H
10
Z1234L
4
Z1234L
11
K1234H
5
K1234H
12
Z1234L
6
Z1234L
13
K0000H
INSTALLATION, OPERATION AND
M A I N T E N A N C E I N S T R U C T I O N S
Product title
CARRIER Model code
Nominal cooling capacity xxx - xxx kW
xx Hz
Product logo
- black and white
Original document
Example:
No. 10: Z1234 L
10 = sequence number
The first letter indicates the plate
direction and gasket position
(Fig. a)
K = strip on left Z = strip on right
Code
Fig. a
Fig. b
Drilling the collectors (Fig. c). Code which indicates the position and the
open or closed status of the collectors.
1234 = open 0 = Closed
e.g.: 1204: indicates that porthole No. 3 is closed.
The last letter indicates the plate type (Fig. b):
H = HIGH EFFICIENCY plate with wide chevron pattern
L = LOW DELTA P plate with narrow chevron pattern
5.10 - Arrangement examples
Legend:
1: Fixed head
4: End plate
2: Movable follower
5: Intermediate plates
3: Initial plate
6: Turning plate
ENGLISH
EN
Fig. c
21

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis