Herunterladen Inhalt Inhalt Diese Seite drucken

Settings - Lenze L-force Drives 8400 motec Montageanleitung

Vorschau ausblenden Andere Handbücher für L-force Drives 8400 motec:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
6

Settings

For initial commissioning, settings can be made via DIP switch and
potentiometer. The settings must be made before mounting the drive unit since
the setting elements cannot be accessed from the outside.
(
Stop!
Automatic motor start
In "Local mode" The auto−start option "Inhibit at power−on" is not
set. When the mains is connected, the motor starts if the controller
enable RFR is bridged or set.
("Local mode" => DIP1/1 = ON and DIP2/5−7 = OFF)
Possible consequences:
ƒ
Protective measures:
ƒ
ƒ
ƒ
EDK84DGDVBxxx4 DE/EN/FR/ES/IT 3.1
Danger or damages through unexpected motor start.
Decouple the motor from the drive train during commissioning
phase.
Replace the factory−set bridge at RFR by an NO contact.
Do not set controller enable.
l
Settings
6
41

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis