Expansion modules
5

Connection

5.1
Conventional detectors and wall tamper
contact (optional)
In case of an EN 50131-3 Grade 3 compliant installation, the
wall tamper is mandatory.
4
Element Description
1
2
3
4
5
5.2
Connection variants for primary lines PL 1 -
PL 6
4
Element Description
1
2
Bosch Security Systems B.V.
Refer to graphic 6 in chapter Graphics, page 4.
Incoming and outgoing LSNs, can be exchanged.
Route the cable shield both ways.
4
If the wall tamper contact is not connected, the WT
bridge (57 + 58) remains plugged in.
When connecting the optional wall tamper
4
contact, remove WT bridge (57 + 58).
A maximum of 20 detectors of the same type can be
connected to a primary line (VdS).
Loop in terminal resistance (EOL) after the last
4
detector:
12k1 for ISP-EMIL-120 and ISP-PCBA-EMIL
4k7 for ISP-EMIL-3RDP
Open collector, 0 V is switched.
Open collector, 12 V is switched.
Refer to graphic 7 in chapter Graphics, page 4.
Intrusion line with terminal resistance (EOL):
12k1 for ISP-EMIL-120 and ISP-PCBA-EMIL
4k7 for ISP-EMIL-3RDP
Contact line without terminal resistance