Herunterladen Inhalt Inhalt Diese Seite drucken

RIB KING 24V Handbuch Seite 33

Mit t2 24v
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 38
B -
SETTINGS
DIP 1
(ON) - MOTOR ROTATION DIRECTION CONTROL (POINT C)
DIP 2
(ON) - TIMER (POINT D)
DIP 3
(ON) - ACTIVATES DOOR RELEASE DURING PHASES OF
SLOWDOWN AND TOTAL OPENING AND CLOSING (AS PER THE
IMPACT TESTS OF EN12453)
DIP 1-2 MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR
TOTAL OPENING (ONLY MODEL CRX) (POINT E)
DIP 1-3 MEMORIZATION/CANCELLATION OF RADIO CONTROL CODES FOR
PEDESTRIAN OPENING (ONLY MODEL CRX) (POINT F)
DIP 2-1 MICRO-SWITCH CONTROLLER FOR PEDESTRIAN OPENING TIMER
DIP 4
Photocells always active (OFF) - Photocells active only during closing
(ON)
DIP 5
Pre-blinking (ON) - Normal blinking (OFF)
DIP 6
Single pulse command (K BUTT) and step-by-step radio receiver (OFF) -
automatic (ON)
DIP 7
Power sensor operation (ON-activated) time operation (OFF-activated).
DIP 8
Electric lock activation (ON-activated)
DIP 9
Electric lock pulse release (ON-activated)
DIP 10 Electric lock pulse engagement (ON-activated)
DIP 11 Easy release activation (ON-activated)
DIP 12 Sensor TEST activation (ON-activated).
DIP 13 Selection of 1 or 2 motor operation (default OFF 2 motors)
DIP 14 KING 24 - ON
DIP 15 KING 24 - OFF
DIP 16 IMMEDIATE CLOSING AFTER PASSING IN FRONT OF PHOTOCELLS
ON
ACTIVATED
OFF
DEACTIVATED
JP1 => Check that the jumper is inserted!
JP2 => Check that the jumper is inserted!
JP3 => Check that the jumper is inserted!
PROG => S3 Programming button
A
DJUSTMENTS
ATTENTION: PUT DIP 3 IN THE ON MODE ONLY AFTER HAVING CARRIED
OUT ALL THE PROGRAMMING PROCEDURES.
NOTE: WITH DIP 3 (ON) BRIEF GATE REVERSAL AFTER IMPACT IS
ACTIVATED.
THIS BRIEF GATE REVERSAL PERMITS STATIC FORCE TO BE REDUCED
TO ZERO WITHIN 5 SECONDS AS PER STANDARD EN12453 POINT A.2.2
(ACCEPTABLE STATIC FORCE), THEREBY COMPLYING WITH THE IMPACT
TESTS ALSO OUTLINED BY EN12453).
IF
COMPLIANCE
WITH
THE
UNNECESSARY, SIMPLY POSITION DIP 3 TO OFF. IN THIS CASE THE GATES
STOP WITHOUT REVERSING.
RUN TRIMMER (TR1) high-speed electronic regulator
This trimmer permits motor speed adjustment (the default setting is maximum
speed). Adjustment of the automation is useful for compliance with European impact
standards.
LOW-SPEED TRIMMER (TR2) Electronic slow speed approach control
The slow speed control is performed by adjusting the LOW- SPEED TRIMMER
which changes the voltage output across the motor(s) (turning it clockwise increases
the speed). Adjustment is performed to determine the correct speed at the end of
opening and closing according to the gate or when there is friction that might cause
the system to function poorly.
AUTOMATIC CLOSING TRIMMER - TCA (TR3) TOTAL OR PEDESTRIAN
default NOT ACTIVATED and LED DL6 OFF (TRIMMER FULLY ROTATED
COUNTERCLOCKWISE)
This trimmer makes it possible to adjust the time for total or pedestrian automatic
closing. Only with gate completely (total) or partially (pedestrian) open and LED DL6
on (trimmer rotated clockwise).
The pause time can be adjusted from a minimum of two seconds up to a maximum
of two minutes.
LED SIGNALS
DL1
program activated (red)
DL2
gate opening M2 (green)
AFOREMENTIONED
STANDARD
DL3
gate closing M2 (red)
DL4
gate opening M1 (green)
DL5
gate closing M1 (red)
DL6
automatic closing indicator (red)
DL7
photocell contact (NC) (red)
DL8
sensor contact (NC) (red)
DL9
STOP button (NC) (red)
DL10 radio code program (green)
FUSES
Fuse 1 T 8A MOTOR PROTECTION FUSE
F1 T 2A
TRANSFORMER PROTECTION FUSE (on the outside of the T2 24V
board)
C -
MOTOR ROTATIONAL DIRECTION CONTROL
1 - Set DIP 1 to ON => LED DL1 starts flashing.
2 - Press and hold the PROG button. (movement is now manually controlled - open-
stop-close-stop-open - etc.) => GREEN LEDS DL2 and DL4 are lit and the gate
panels open with a fixed lag of 2 sec. If they close instead of open, release the
button and reverse the two wires on the motor used.
3 - After opening release the PROG button and calibrate the mechanical opening
stops (on the operator).
4 - Press and hold the PROG button => RED LEDs DL3 and DL5 turn on and the
gate panels close with a time lag of 2 sec.
5 - Continue to hold the PROG button until the gate is completely closed.
6 - Leave the two doors completely closed to set the timer.
7 - Reset DIP1 to OFF => LED DL1 turns off, signaling exit from control.
N.B.: During this check the stop, the photocells and the sensors are not active.
D -
SETTING THE TIMER FOR 2 MOTORS (#) WITH POWER
SENSOR ACTIVATED (DIP 7 ON)
WHILE SETTING THE TIMER THE POWER SENSOR IS CONTINUOUSLY
ACTIVATED.
1 - The gate must be completely closed.
2 - Set DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button. => M1 opens.
4 - When the mechanical opening stop is reached, the AUTOMATIC POWER
SENSOR stops M1 (memorizing the time and the power) => At the same time
M2 is triggered to open.
5 - When the mechanical opening stop is reached, the AUTOMATIC POWER
SENSOR stops M2 (memorizing the time and the power).
6 - Press the PROG button. => M2 closes.
7 - Press the PROG button. => M1 closes and sets the lag time between M2 and M1.
At the same time LED DL1 stops flashing indicating exit from the programming
procedure.
Safety and other gate commands now operate normally (inversions, stop,
IS
alarms, etc.).
8 - The gate panels will close in high-speed mode (depending on how you set the
RUN trimmer) and near total closure in the slow mode (depending on how you
set the LOW-SPEED trimmer).
9 - Upon closing the power sensors stop the gate.
10 - AFTER PROGRAMMING RESET DIP 2 TO OFF.
D -
SETTING THE TIME FOR ONE MOTOR (M1) (#) WITH POWER
SENSOR ACTIVATED (DIP 7 ON)
CAUTION: FOR ONE MOTOR CONTROL DIP 13 MUST BE POSITIONED TO ON;
DURING PROGRAMMING THE POWER SENSOR IS CONTINUOUSLY ACTIVE.
The gate must be completely closed.
1 - Set DIP 2 to ON => LED DL1 will blink rapidly.
2 - Press the PROG button. => M1 opens.
When the mechanical opening stop is reached, the AUTOMATIC POWER
SENSOR stops M1 (memorizing the time and the power).
3 - Press the PROG button. => M1 closes.
At the same time LED DL1 stops flashing indicating exit from programming.
Safety and other gate commands now operate normally (inversions, stop,
alarms, etc.).
Upon closing the power sensor stops the gate.
4 - AFTER PROGRAMMING RESET DIP 2 TO OFF.
(#) DURING PROGRAMMING THE SAFETY DEVICES ARE ACTIVE AND STOP
THE PROGRAMMING PROCEDURE (LED DL1 FROM FLASHING BECOMES
CONSTANT). TO REPEAT PROGRAMMING SET DIP 2 TO OFF, CLOSE
THE GATE USING THE PROCEDURE "MOTOR ROTATIONAL DIRECTION
CONTROL" AND REPEAT THE DESIRED PROGRAMMING PROCEDURE.
33
33
G
B

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

King 24v l

Inhaltsverzeichnis