Technical specifications
General
CU-5MX1
Nominal cooling
(kW)
(1)
capacity
Nominal heating
(kW)
(2)
capacity
Nominal input cooling/
(kW)
6.10/5.67
(3)
heating
Dimensions HxWxD
(mm)
1440x635x690
Weight
(kg)
Connections
• refrigerant gas inlet
(inch)
(mm)
3/8 flare
• refrigerant liquid outlet
(inch)
(mm)
(1) The nominal cooling capacity is based on:
- indoor temperature: 27°CDB/19°CWB
- outdoor temperature: 35°CDB
- pipe length: 5m
- level difference: 0m
(2) The nominal heating capacity is based on:
- indoor temperature: 20°CDB
- outdoor temperature: 7°CDB/6°CWB
- pipe length: 5m
- level difference: 0m
(3) The nominal input includes total input of the unit: compressor, fan motor
and control circuit.
Compressor
Model
Oil type
DAPHNE FVC68D
Oil charge volume
(l)
Crankcase heater
(W)
Refrigerant type
Refrigerant charge
(kg)
Condenser
Nominal air flow
3
(m
/min)
Fan motor output
(W)
(1)
Electrical specifications
Model
Power supply
• Phase
• Frequency
(Hz)
• Voltage
(V)
• Voltage tolerance
(%)
• Recommended fuses
(A)
Compressor
• Phase
• Frequency
(Hz)
• Voltage
(V)
• Nominal running current
(A)
Control and fan motor
• Phase
• Frequency
(Hz)
• Voltage
(V)
• Nominal running current
(A)
(1) Refer to the engineering data book for the complete list of specifications.
CU-5~10MX1SPP
Urban Multi air conditioner
4PW12336-1C
CU-8MX1
CU-10MX1
14.0
22.4
28.0
16.0
25.0
31.5
9.43/8.66
11.8/11.0
1220x1280x690 1440x1280x690
137
227
248
3/4 OD
1 OD
1-1/8 OD
19.1
25.4
28.6
1/2 flare
1/2 flare
9.5
12.7
12.7
CU-5MX1
CU-8MX1
CU-10MX1
JT100BEVTYE +
JT100BEVTYE +
JT100BEVYE
JT100BETYE
JT160BETYE
DAPHNE FVC68D
DAPHNE FVC68D
1.2
1.5+1.4
1.5+1.7
33
33+33
33+33
R-407C
R-407C
R-407C
6.3
9.6
11.2
CU-5MX1
CU-8MX1
CU-10MX1
80
150
170
190
140+230
190+230
CU-5MX1
CU-8MX1
CU-10MX1
3N~
3N~
3N~
50
50
50
400
400
400
+/-10
+/-10
+/-10
20
32
40
3~
3~
3~
50
50
50
380-415
380-415
380-415
10.6-10.1
17.0-15.9
18.2-16.9
1~
1~
1~
50
50
50
220-240
220-240
220-240
1.5
2.5
2.5
M
AIN COMPONENTS
For main components and function of the main components, refer to
the Engineering Data Book.
S
ELECTION OF LOCATION
This unit, both indoor and outdoor, is suitable for installation in a
commercial and light industrial environment. If installed as a house-
hold appliance it could cause electromagnetic interference.
The inverter units should be installed in a location that meets the
following requirements:
1
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
2
The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (Refer to
figure 1 and choose one of both possibilities).
3
There is no danger of fire due to leakage of inflammable gas.
4
Ensure that water cannot cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).
5
The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length. (See "Example of
connection" on page 6).
6
Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.
Make sure that the air inlet and outlet of the unit are not
7
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.
In heavy snowfall areas, select an installation site where
snow will not affect operation of the unit.
The refrigerant R-407C itself is nontoxic, nonflammable
and is safe. If the refrigerant should leak however, its
concentration may exceed the allowable limit depending on
room size. Due to this it could be necessary to take
measures against leakage. Refer to "Caution for refrigerant
leaks" on page 12.
When the wireless kit is used, the transmission distance
from the remote controller may be shortened if a rapid start
fluorescent lamp (electronic lighting type or inverter type)
is installed in the room. Install the indoor unit as far as
possible from the fluorescent lamp.
Installation manual
3