Herunterladen Inhalt Inhalt Diese Seite drucken

Energy Consumption Data; Data Table - STIEBEL ELTRON HSBB 3 Bedienung Und Installation

Speicher- und hydraulikmodul
Vorschau ausblenden Andere Handbücher für HSBB 3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

INSTALLATIoN
Specification

16.3 Energy consumption data

The product data complies with EU regulations relating to the
directive on the ecodesign of energy related products (ErP).
Manufacturer
Energy efficiency class
Standby losses
Cylinder capacity

16.4 Data table

Power consumption
Max. power consumption, circulation pump on the
heating side
Power consumption, emergency/booster heater
Hydraulic data
Surface area, indirect coil
External available pressure differential at 1.0 m³/h
External available pressure differential at 1.5 m³/h
External available pressure differential at 2 m³/h
External available pressure differential at 2.5 m³/h
Cylinder capacity
Nominal capacity
Energy data
Energy efficiency class
Standby energy consumption/24 h at 65 °C
Electrical data
Rated voltage, control unit
Rated voltage, emergency/booster heater
Control unit phases
Emergency/booster heater phases
Control unit fuse/MCB
MCB/fuse protection, emergency/booster heater
Versions
Suitable for
Suitable for
IP rating
Dimensions
Height
Width
Depth
Height when tilted
Heat transfer area
Weights
Weight, full
Connections
Connection on the heating side
Cold water connection
DHW connection
40
| HSBB 3
HSBB 3
234264
STIEBEL ELTRON
C
W
79
l
189
HSBB 3
234264
W
72
kW
8.8
3.3
hPa
700
hPa
567
hPa
374
hPa
101
l
189
l
168
C
kWh
1.9
V
230
V
400
1/N/PE
3/N/PE
A
1 x B 16
A
3 x B 16
Heat pump
Air-water
heat pumps
07-17 ACS
classic
IP20
mm
1780
mm
600
mm
650
mm
1810
2.4
kg
332
22 mm
22 mm
22 mm
Heating water quality requirements
Water hardness
pH value (with aluminium fittings)
pH value (without aluminium fittings)
Conductivity (softening)
Conductivity (desalination)
Chloride
Oxygen 8-12 weeks after filling (softening)
Oxygen 8-12 weeks after filling (desalination)
Values
Nominal heating flow rate at A-7/W35 and 7 K
Heat loss
Min. heating flow rate
Max. operating pressure
Permissible operating pressure, heating circuit
Permissible operating pressure, DHW
Expansion vessel volume
HSBB 3
°dH
≤3
8.0-8.5
8.0-10.0
μS/cm
<1000
μS/cm
20-100
mg/l
<30
mg/l
<0.02
mg/l
<0.1
m³/h
1.4
kW/24 h
1.78
m³/h
0.7
MPa
1.0
MPa
0.3
MPa
1.0
l
18
www.stiebel-eltron.com

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis