Power supply

11.7.1 Permissible materials
Cold water line
Galvanised steel, stainless steel, copper and plastic are approved
materials.
DHW line
Stainless steel, copper and plastic pipework are approved.
Material losses
!
The maximum permissible pressure must not be exceed-
ed (see chapter "Specification / Data table").
Safety valve on the domestic hot water side
f Install a type-tested safety valve in the cold water supply
f
line. Please note that, depending on the supply pressure, you
may also need a pressure reducing valve.
f The safety valve discharge aperture must remain open to
f
atmosphere.
f Install the safety valve drain pipe with a constant fall to the
f
drain.
f Size the drain so that water can drain off unimpeded when
f
the safety valve is fully opened.
f Flush the pipes thoroughly.
f
11.8 High limit safety cut-out for area heating
system STB-FB
Material losses
!
In order to prevent excessively high flow temperatures
in the area heating system causing damage in the event
of a fault, install a high limit safety cut-out to limit the
system temperature.
12. Power supply
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
WARNING Electrocution
f Before working on the appliance, isolate it from the
f
power supply at the control panel.
WARNING Electrocution
Only use a permanent connection to the power supply.
Ensure the appliance can be separated from the power
supply by an isolator that disconnects all poles with at
least 3 mm contact separation. This requirement can be
met with contactors, circuit breakers, fuses/MCBs, etc.
Material losses
!
Provide separate fuses for the two power circuits of the
appliance and the control unit.
32
| HSBB 3
Material losses
!
The specified voltage must match the mains voltage. Ob-
serve the type plate.
Note
Electrical connection work must only be carried out by
a qualified contractor and in accordance with these in-
structions.
Note
Permission to connect the appliance may need to be ob-
tained from your local power supply utility.
f Observe VDE 0100 [or local regulations] and the reg-
f
ulations of your local power supply utility.
Note
If there is an emergency/booster heater (DHC) integrated
into the heat pump, connect it directly in the heat pump.
1 Cable entry
The wiring chamber of the appliance is located behind the lower
appliance door. If the lower appliance door is closed, see chapter
"Opening the appliance".
f Route all connecting cables and sensor leads through the
f
cable entry into the appliance.
f Route all connecting cables and sensor leads through the
f
gap in the centre of the appliance so they reach as far as the
connection PCB.
f Connect the cables and sensor leads as detailed below.
f
f Use cables with the relevant cross-sections. Observe the ap-
f
plicable national and regional regulations.
1
www.stiebel-eltron.com