Herunterladen Inhalt Inhalt Diese Seite drucken

Connecting To External Equipment - Panasonic CZ-64ESMC3 Installationshandbuch

Vorschau ausblenden Andere Handbücher für CZ-64ESMC3:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 72
Wiring

Connecting to external equipment

 Keep the signal input line lengths to 100 meters or less. For distances greater than
this, use a relay.
Input/Output
Name
item
Status
output
Control
input
Signal terminal board
14
(EN)
(continued)
System controller side
Condition
Non-voltage contact "a"
Static (Relay output)
Contact allowable voltage:
Max. DC30 V
Contact allowable current:
Max. 0.5 A
Minimum application load:
DC5 V 1 mA
All stop:
Voltage contact "a" Pulse
(When batch stop input is
ON, the stop signal is sent
periodically.)
Pulse width:
300 msec or more
All operation:
Voltage contact "a" Pulse
Pulse width:
300 msec or more
Demand 1 input,
Demand 2 input
Voltage contact "a" Static
Contact allowable voltage:
DC24 V±10 %
Contact allowable current:
Max. 10 mA
Terminal name
Output
Alarm output
(DO 1)
Operation output
(DO 2)
Common1
(COM 1)
Input 1
All stop input
(Di 1)
All operation input
(Di 2)
Common 2
(COM 2)
Input 2
Demand 1 input
(Di 3)
Demand 2 input
(Di 4)
Common 3
(COM 3)
INPUT 1
INPUT 2
A
B
C
D
E
G
H
OUTPUT
External equipment
side
Circuit example
A. Common 2 (COM 2)
B. All stop input (Di 1)
F
C. All operation input (Di 2)
D. Common 3 (COM 3)
E. Demand 1 input (Di 3)
F. Demand 2 input (Di 4)
G. Common 1 (COM 1)
I
H. Alarm output (DO 1)
I. Operation output (DO 2)
DC24 V
COM
DC24 V
COM