WARNING
The appliance disconnection must be incorporated with an all-pole disconnection device in the
•
Any person who is involved with working on or breaking into a refrigerant circuit should hold a
•
competence to handle refrigerants safely in accordance with an industry recognised assessment
• Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried out
• The appliance shall be stored so as to prevent mechanical damage from occurring.
•
• Keep ventilation openings clear of obstruction.
NOTE: The following informations are required for the units adopt R32/R290 Refrigerant.
• The appliance shall be stored in a room without continuously operating ignition sources
• Do not pierce or burn.
•
Be aware that the refrigerants may not contain an odour.
•
Compliance with national gas regulations shall be observed.
•
Appliance shall be stored in a well-ventilated area where the room size corresponds to the room
•
(Please see the following form ). The appliance shall not be installed in an unventilated space, if
that space is smaller than X m ² (Please see the following form ).
Model
(Btu/h)
≤30000
≤30000
≤30000
30000-48000
30000-48000
30000-48000
>48000
>48000
>48000
Page 6
Amount of refrigerant
to be charged (kg)
≤2.048
≤2.048
≤2.048
2.048-3.0
2.048-3.0
2.048-3.0
>3.0
>3.0
>3.0
maximum installation
height (m)
2.2m
1.8m
0.6m
2.2m
1.8m
0.6m
2.2m
1.8m
0.6m
²
Minimum room
area (m²)
4
4
35
4
8
80
5
9
80