oFPA -- Offline parameters

Contents
Parameters defining basic functions, such as display
elements, limit values, safety values, etc. They come into
effect after exiting to process control level.
Step
Accessing the
1
oFPA list
2
3
4
Modification
of parameters
5
6
Exit to process
7
control level
8
oFPA - - Offline parameter list
Parameter
Decimal point w/x display
Start of scale value
Full scale value
Alarm 1
Alarm 2 (A2≤A1)
Alarm 3
Alarm 4 (A4≤A5)
Alarm hysteresis
Setpoint start of scale
Setpoint full scale
Safety setpoint
Setpoint ramp time
Ratio factor -- start
Ratio factor -- end
Safety manipulated
variable
Split range left (Y1≤Y2)
Split range right
Initial value for lineariser
L--1 (--10 %) to L11
(110 %) are equidist input
vertices
(1) Note: If S21=5, values
are standardized to dA to
dE.
1)
Decimal point
1)
Start of scale value
1)
Full scale value
1)
effective as of software version --A9, only with ratio controller (S1 = 3)
indicator range of controller variable x1 and the evaluated leading process variable w.
SIPART DR21
C73000-B7474-C141-07
Procedure
Press pushbutton
(6) for about 6 seconds until
"PS" starts to flash. Release pushbutton -- "onPA"
displayed (Selection Level). Blocked if digital si-
gnal bLPS=1.
Press pushbutton
(15) several times
until "oFPA" is displayed (Selection Level).
Blocked if digital signal bLS=1.
Press pushbutton
(11) for about 3 seconds
(Configuring Level). Controller is now blocked and,
the most recent value of y will be retained.
Using pushbutton
(7) or
ter names from y digital indicator (9).
Using pushbutton
(15) or
ters values in the w/x digital indicator (3).
Repeat steps 4 and 5 until all desired parameters
are set.
Press pushbutton
(16) once (Selection Level).
Press pushbutton
(16) once (Process Control
Level). Controller is now in manual mode.
y ind.
Param.
name
Min.
dP
_.------
dA
--1999
dE
--1999
A1
--110 % bis 110 %
A2
of dA, dE if
A3
S76/S77 =
A4
0/2/3/4/5
HA
0.1
SA
--10 % to110 %
SE
de dA, dE
SH
tS
oFF/0.100
vA
0.000
vE
0.000
YS
--10.0
Y1
0.0
Y2
0.0
L--1
--10.0
L0
--10.0
L1
--10.0
L2
--10.0
L3
--10.0
L4
--10.0
L5
--10.0
L6
--10.0
--10.0
L7
--10.0
L8
--10.0
L9
--10.0
L10
--10.0
L11
Pd
_.------
Ad
--1999
Ed
--1999
3.2
(8), select parame-
(14), modify parame-
w/x indicator
Factory
Eng.
Max.
setting
unit
--------
.--
0.0
9999
100.0
9999
5.0
--5.0
5.0
--5.0
10.0
1.0
--5.0
105.0
0.0
9984
oFF
9.999
0.000
9.999
1.000
110.0
0.0
100.0
50.0
100.0
50.0
110.0
--10.0
% (1)
110.0
0.0
% (1)
110.0
10.0
% (1)
110.0
20.0
% (1)
110.0
30.0
% (1)
110.0
40.0
% (1)
110.0
50.0
% (1)
110.0
60.0
% (1)
110.0
70.0
% (1)
110.0
80.0
% (1)
110.0
90.0
% (1)
110.0
100.0
% (1)
110.0
110.0
% (1)
.--
--------
9999
0.0
9999
100.0
--
%
min
1
1
%
%
%
--
39