Hydro Unit
Refrigeration pipe
The length and height of the refrigeration pipe must be
within the following values.
As long as the Hydro Unit is installed within these
ranges, no additional refrigerant is required.
▼ Fig. 7-08
Outdoor unit
Hydro Unit
Model
4.5 kW
Hydro Unit
8 & 14 kW
Hydro Unit
Refrigerant pipe sizes
Hydro Unit Model
4.5 kW Hydro Unit
8 & 14 kW Hydro Unit
Flaring
• Cut the refrigerant pipes to the correct length using a
pipe cutter. Remove any burrs that may be on the
pipes as these may cause refrigerant leaks or
component failure in the refrigeration cycle.
• Place the correct size flare nuts onto the pipes (use
the flare nuts supplied with the Hydro Unit or use
flare nuts designed specifically for R410A
refrigerant) and then flare the pipes using the correct
flaring tool.
15-EN
H:Max
L:Max L:Min
±10 m
15 m
(above or below)
±30 m
30 m
(above or below)
Liquid Side
Gas Side (mm)
(mm)
Ø 12.7
Ø 6.35
Ø 15.88
Ø 9.52
Tightening
• Connect the refrigerant pipes, from the outdoor unit,
to the Hydro Unit as shown below.
▼ Fig. 7-09
• Align the flare connection on each pipe with the
corresponding outlet connection on the Hydro Unit.
Tighten the flare nuts, using fingers, to secure the
pipes in place.
5 m
• Tighten the flare nuts, using a torque wrench, to the
tightening torques shown below:
5 m
Outer Ø of Copper Pipe
(mm)
Ø 6.35
Ø 9.52
Ø 12.7
Ø 15.88
• To prevent damage, to the refrigerant pipes, use two
spanners to tighten the flare nut connections to the
required torque.
 Water pipe
WARNING
• Install water pipes according to the regulations of
respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure
resistance.
The setting value of the overpressure preventive valve
is 0.43 MPa. (4.3 bar)
CAUTION
• Do not use zinc plated water pipes. When steel pipes
are used, insulate both ends of the pipes.
• The water to be used must meet the water quality
standard specified in EN directive 98/83 EC.
– 15 –
Installation Manual
Gas line
Liquid line
Tightening Torque (N/m)
14 to 18
33 to 42
50 to 62
63 to 77