Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connections - Sabiana LC-15-W Handbuch Für Installation, Gebrauch Und Wartung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

- ELECTRICAL
CONNECTIONS
General instructions
• Before installing the air curtain unit, make sure the rated voltage of the power supply is 230V - 50 Hz.
• Make sure that, in addition to supplying the working current required by the fan coil, the mains electrical supply is
also able to supply the current necessary to operate other household appliances and units.
• Perform electrical connections in accordance with laws and regulations in force in the country concerned.
The unit must always be earthed.
Always disconnect the electrical power supply before opening the unit.
version
Connect the "Control side" with
dorsal 230Vac 50Hz.
Recommended cable section 1,5 mm
version
Connect the "Control side" with
dorsal 230Vac 50Hz.
Recommended cable section 1,5 mm
version
Connect the "Control side" with
dorsal 230Vac 50Hz.
Connect the "Power side" with
dorsal appropriate 400Vac 50Hz 3P.
Recommended cable section
Type
Output
Voltage
[kW]
[V]
Power Side
LC 10 - E
8
400V3~
LC 15 - E
12
400V3~
LC 20 - E
16
400V3~
SEE THE WIRING AND THE MANUAL SECTION DEDICATED BY MODEL AIR CURTAIN UNIT PURCHASED.
Attention!: check absorption machine.
2
.
2
.
POWER SIDE
400 Vac 50 Hz 3P
Minimum
Section
2
[mm
]
2,5
4
4
CONTROL SIDE
230 Vac 50 Hz
CONTROL SIDE
230 Vac 50 Hz
CONTROL SIDE
230 Vac 50 Hz
English