ATTENTION! : To carry out the electrical connections
to the T–MB control,remove the insulated protection
device from the clamp. Once the electrical connections
are completed, replace the protection device, as in Fig. 2.
Reassemble the front part of the control, placing
CONTROL WIRING CONNECTIONS
The control panel must be wired to the power board
located inside the electrical compartment of the unit,
complying with the correspondence of the common
numbering to both boards.
Use 3 conductors with 0,5 mm2 section.
NOTE:
metres in length.
SELV Board
7
7
RESPECT THE RIGHT WIRING SEQUENCES
6
5
6
5
T-MB
T-MB
SETTING DIP SWITCHES
1
ON
OFF
Set DIP can be used to modify the functions performed
by the controller (as shown in the table below).
ON
DIP
DEFAULT
Not
Not
1
1
OFF
OFF
used
used
Select the temperature sensor
2
OFF
fitted on the appliance
AIR CURTAIN
3
3
ON
ON
Configuration
AU / AIR CURTAIN
4
4
ON
ON
Configuration
Dip dedicated to manufacturer
ENABLE ROOM AIR TEMPERATURE PROBE
- DIP Nr. 2 -
In particular, DIP NR. 2
be used.
In fact, an air probe (T1 probe) is installed on the intake
of the cassette and fancoil devices.
The T–MB control is also equipped with air probe.
- DIP nr. 2 OFF
The inside T-MB sensor is activate;
- DIP nr. 2 ON
The T1 probe, connected to the device main board
(intake air probe) is activated.
Selv Board
2
3
4
POSIZIONE
OFF
Not
Not
used
used
Select the temperature sensor
fitted on the T–MB
AU Configuration
MB Configuration