Herunterladen Inhalt Inhalt Diese Seite drucken

Indoor Unit Installation - Toshiba RAS-10SKVP-ND Einbauanleitung

Vorschau ausblenden Andere Handbücher für RAS-10SKVP-ND:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 35
InstallationManual.book Page 11 Tuesday, January 9, 2007 3:22 PM

Indoor Unit Installation

1.
Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2.
Swing the indoor unit to right and left to confirm that it is firmly hooked on the installation plate.
3.
While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to
confirm that it is firmly hooked on the installation plate.
• For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing the bottom up at the specified
places.
Drainage
1.
Run the drain hose at a downward sloped angle.
NOTE
• Hole should be made at a slight downward slant on the outdoor side.
2.
Put water in the drain pan and make sure that the water is being drained outside.
3.
When connecting extension drain hose, insulate the connection part of extension drain hose with shield pipe.
CAUTION
Install the drain pipe for proper drainage. Improper drainage can result in water dripping inside the room.
This air conditioner has been designed to drain water collected from
condensation which forms on the back of the indoor unit, to the drain pan.
Therefore, do not locate the power cord and other parts at a height above the
drain guide.
Hook here
a Installation plate
Hook
Push
Do not route the
drain hose upwards.
50 mm or
more
Do not put the drain hose
end into water.
Shield pipe
Inside the room
Drain hose
Press (unhook)
Push
Do not form the drain
hose into a waved shape.
Do not put the drain hose
end in a drainage ditch.
Extension drain hose
Space for pipes
11
Wall
Drain guide
EN

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis