Operating instructions
GB
Adjustment and Starting Up – easyControls
Stop time in hours:
If it is not possible to reach the set value within 2 hours, the humidity control will
be deactivated for the stop time.
Setting range between 0-24 hours; step size 1 hour.
CO
CONTROL
Options: The status of the CO
2
"Off", "Stepped" or "Continuous".
"Off" CO
"Stepped" CO
"Continuous" CO
Depending on the CO
2-3-4) between voltage stage 0 and voltage stage 4. The percentage control is
displayed on the web server page or on the comfort controller KWL-BEC (Factory
setting: Continuous).
Set value:
Adjustable limit value of CO
Setting range between 300-2000 ppm; step size 50 ppm.
Switching steps:
The threshold indicates when the next fan stage will be activated, e.g. set value
1000 ppm, switching step 150 ppm. If the measured value is between 850-1000
ppm, stage 1 will be activated. If the CO
ppm, the next stage will be activated (stage 2).
Setting range between 50-400 ppm; step size 50 ppm.
VOC CONTROL
Options: The status of the VOC control can be configured to
"Off", "Stepped" or "Continuous".
"Off" VOC control deactivated
"Stepped" VOC control active with stepped control logic
"Continuous" VOC control active with continuous control logic
Depending on the VOC level, the fans are continuously regulated (fan stages 0-1-
2-3-4) between voltage stage 0 and voltage stage 4. The percentage control is
displayed on the web server page or on the comfort controller KWL-BEC (Factory
setting: Continuous).
Set value:
Adjustable limit value of VOC concentration.
Setting range between 300-2000 ppm; step size 50 ppm.
(Factory setting: 800 ppm)
Switching steps:
The threshold indicates when the next fan stage will be activated, e.g. set value
1000 ppm, switching step 150 ppm. If the measured value is between 850-1000
ppm, stage 1 will be activated. If the VOC concentration increases to 1000-1150
ppm, the next stage will be activated (stage 2).
Setting range between 50-400 ppm; step size 50 ppm
22
control can be configured to
2
control deactivated
2
control active with stepped control logic
2
control active with continuous control logic
2
level, the fans are continuously regulated (fan stages 0-1-
2
concentration.
2
concentration increases to 1000-1150