Maintenance of the unit

Maintenance of the SAVE VTC 700 should normally be performed 3 - 4 times a year. Apart from general cleaning the
following should be observed:
6.1

Warnings

Danger
• Make sure that the mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• All electrical connections and maintenance work must be carried out by an authorized installer and in
accordance with local rules and regulations.
Warning
• This product must only be operated by a person who has suitable knowledge or training within this field
or carried out with the supervision of a suitably qualified person.
• Beware of sharp edges during mounting and maintenance. Use protective gloves.
Warning
• All though the mains supply to the unit has been disconnected there is still risk for injury due to rotating
parts that have not come to a complete standstill.
6.2

Removing the front inspection hatch

Remove the front hatch by the use of an 8 mm Allen key, after which the
hatch is tilted back and lifted off completely.
6.3

Changing Outdoor/Extract air filters

The filters cannot be cleaned and must be changed as necessary. This is normally done 1–2 times per year depending
on the air pollution at the installation site.
The factory installed filters are of filter quality M5/ePM10 50% for the supply air and M5/ePM10 50% for the extract
air filter. The filters need to be replaced when polluted. New sets of filters can be acquired from your installer or