8 EN – Quick installation and start-up guide
Select the power cables
Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.

Ensure the cooling

See tables
I
and
of the drive without derating is -15 to +40 °C (+5 to +104 °F). No condensation or
frost is allowed. For restrictions below 0 °C (+32 °F) and above +40 °C (+104 °F),
see chapter Technical data in ACS580-01 user's manual (3AUA0000076333
[English]).
EN
Protect the drive and input power cable
DA
See tables III,
IV
DE
If you are going to use gG fuses, check on the fuse time-current curve to ensure the
operating time of the fuse is below 0.5 seconds. Follow the local regulations.
ES
Install the drive on the wall
FI
See figures
A1
FR
Note: You can use only two screws instead of four to attach the lower part of the
drive.
IT
Check the insulation of the input and motor cables and the
NL
motor
PT
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
RU
Check the insulation of the motor cable and motor when the cable is disconnected
SV
from the drive. Measure the insulation resistance between each phase conductor and
the Protective Earth conductor using a measuring voltage of 1000 V DC. The
TR
insulation resistance of an ABB motor must exceed 100 Mohm (reference value at
25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturer's
CN
instructions.
II
on page
5
for the losses. The allowed operating temperature range
and
V
on pages
5
and
A2
on page 3.
and
6
for the fuses.