Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V) .
Wire sizes: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m
Install optional modules, if any
See chapter Electrical installation in ACS580-01 user's manual (3AUA0000076333
[English]).
Check the compatibility with IT (ungrounded) and corner-
grounded TN systems
WARNING! Do not install the drive with the internal EMC filter connected on an
IT system (an ungrounded power system or a high-resistance-grounded [over
30 ohms] power system) or on a corner-grounded TN system.
If you connect the drive to an IT (ungrounded) or a corner-grounded TN system,
disconnect the EMC filters before connecting the drive to the supply network. For
information on how to do it, see chapter Electrical installation in ACS580-01 user's
manual (3AUA0000076333 [English]).
Reinstall covers
See figure G.
1. Install the cover of the cable entry box.
2. Tighten the two retaining screws with a screwdriver.
3. Reinstall the module cover. Put the tabs on the cover top in their counterparts on
the housing and then press the cover.
4. Tighten the two retaining screws with a screwdriver.