4.3

Adjustable parameters

The following parameters can be set on the meter:
Reset error message F8 (only displayed if F8 appears)
Reset maxima
Reset missing time and flow measurement time
Enter yearly set day (DD, MM) *
Enter monthly set day (DD) *
Enter date (DD, MM, YY) *
Enter time (hh, mm, ss) *
Enter 8-digit property number (corresponds to M-Bus second-
ary address)
Enter M-Bus primary address for module 1
(0..255) *
Enter M-Bus primary address for module 2
(0..255) *
Select first module function for module 1
(CE or C2)
Select second module function for module 1
(CV or CT or RI)
Select first module function for module 2
(CE or C2)
Select second module for module 2
(CV or CT or RI)
Select maxima measurement period
(7.5, 15, 30, 60 min / 3, 6, 12, 24 h)
Return to normal mode
* Ensure that sensible values are entered. The meter does not carry out a plausibility test.
This means that incorrect values can also be entered (e. g. month > 12).
Note: The meter can be parameterised even if the mod-
ules have not yet been installed.
4.4
Call up parameter operation
Proceed as follows to call up the parameter operation:
Hold the service button for 3 seconds until
appears on the LCD.
Press button 1 to switch the display until
appears on the LCD.
Press button 2 to select the menu.
Note: To reset error F8 or the maxima press button 2.
4.5
Selecting parameters
To select a parameter proceed as follows:
To switch the display press button 1.
To activate the parameter to be changed press button 2.
Siemens Building Technologies
4.6
Parameterisation
For parameterisation proceed as follows:
To change the blinking value press button 2.
To enter the set value press button 1.
The next digit to the right blinks. Repeat the steps above for all
digits.
The LCD displayes a star symbol briefly to confirm.
If inputs are incorrect, parameterisation can be repeated.
4.7
Completing parameterisation
To leave the parameterisation operation proceeds as follows:
Hold button 1 until the LCD shows
Press button 2.
4.8
Cancelling Input
To close the parameterisation proceeds as follows:
Press the service button during parameterisation (ESC
function).
The LCD display shows the last valid value.
4.9
Service software
With the service software, tariffs, fast pulses and communica-
tion modules can be set in parameterisation mode.
5.

Getting started

For activation proceed as follows:
Put the housing cover in position and press it gently until all
the lugs click into place audibly.
Open the slide valves slowly.
Check the heating system for leak-tightness and bleed air
out carefully.
The message "F0" disappears after 100 sec. at the most.
Check the measured values for flow and temperatures for
plausibility.
Vent the heating system until the flow display is stable.
Regulate the heating system with the flow display.
Seal the electronic unit to protect against manipulation.
Fit the user locks to the electronic unit.
Read the meter status for energy, volume, operation and
missing time and note the values.
Recommendation: Reset the maxima and the missing time.
CE2M5324xx
.
15.05.2015 13