Programming Instructions
KINAX N702-INOX HART via the HART Field Communicator 475
KINAX N702-INOX HART may be very easily program-
med via commercially available HART field communi-
cators (e.g. Emerson type 475).
1. Commissioning
1.1 Connection
Connect the HART field communicator 475 directly to
the 4...20mA 2-wire signal line of KINAX N702-INOX
HART. The measuring circuit must have a minimum
apparent resistance of 240Ω.
R
L
Transmitter-
power supply
unit
24V
1.2 Switch on
Switch on HART Field Communicator 475
Select operating mode HART
Confirm with YES
HART
Communicator
Your are now in the display mode
1.3 Set zero point (43 Set Primary Variable Zero)
Select Device setup
Select Diag/Service
Select Zero trim
Set zero point and confirm with OK.