When the "Battery Failure" indication is displayed,
replace the battery as follows:
1. Lever the cover of the battery compartment out of
the socket with a suitable tool (e.g. precision engi-
neer screwdriver 2.0 mm).
Figure 14-1 Removing the cover of the battery compartment
2. Use an appropriate non-conducting tool (for
example plastic tweezers) to pull the battery out of
the compartment.
WARNING
Warning of explosion hazard in the case of batteries
that are not fully discharged
Non-observance may lead to death or serious
injury.
To avoid a short circuit on the battery contacts, the
battery may only be removed with a non-conductive
tool.
3. Dispose of the battery as explained on the next
page.
4. Remove the new battery type PANASONIC CR2032
or VARTA 6032 101 501 from the packaging (check
the expiry date on the packaging)
5. Insert the battery carefully into the battery
compartment with the polarity indicated above the
32
SICAM MMU 7KG9663, Product Information
E50417-B1050-C514-A2, Edition 04.2013
Cover of
battery