Technical data:
Model
Working area, humidity
Working area, temperature
Air volume at max. external
pressure
Power supply
Max. power consumption
Max. ampere consumption
Refrigerant
Quantity of refrigerant
Noise level* (1 m away from
unit)
Weight
Dimensions, H × L × W
Measured opposite to the duct openings
*)
-
CDP 35T
%RF
40-100
°C
10-36
m
/h
250
3
V/Hz
1 × 230/50
kW
0,72
A
2.8
-
R407C
kg
0.6
dB(A)
44
kg
57
mm
680 × 890 ×
290
CDP 45T
CDP 65T
40-100
40-100
10-36
10-36
500
750
1 × 230/50
1 × 230/50
1,05
1,65
4.3
7.2
R407C
R407C
0.95
1.6
46
48
68
95
680 × 1200 ×
680 × 1735 ×
290
290