Type
Relay
output
Digital
input
Switching
input
Reproduction of the motor's condition via relays 1 and 2
Relay 1 is closed if there is no motor error and relay 2 is closed if
the pump is running.
The reproduction of the motor's condition does not offer 100 %
safety; this can only be guaranteed by the flow or pressure
sensors.
09|2018
Terminal
Terminal
description
A11
NC contact
Relay 11
B11
Base relay 11
C11
NO contact
Relay 11
A12
NC contact
Relay 12
B12
Base relay 12
C12
NO contact
Relay 12
50
24 V DC
output for Inx,
Alnx
51-56
Digital input
11 - 16
59
Reference
potential
digital input
61
Analogue
input 11
0 - 10 V
2 - 10 V
62
Analogue
input 12
0 - 20 mA
4 - 20 mA
69
Reference
potential
analogue input
Cable cross-
Cable cross-
section rigid
section
flexible
0,5 - 1,5 mm²
0,5 - 1,5 mm²
Wire end
ferrule 0,5 - 1,0
mm²
Wire end
ferrule with
plastic sleeve
0,5 mm²
0,5 - 1,5 mm²
0,5 - 1,5 mm²
Wire end
ferrule 0,5 -
1,0 mm²
Wire end
ferrule with
plastic sleeve
0,5 mm²