5
ELECTRICAL WIRING
6
5.3. SETTINGS OF DIP SWITCHES
Quantity and Position of Dip Switches
Dips switches position is the following:
RSW
DSW7
DSW3
CAUTION:
Before setting dips switches, firstly turn off power
source and set the position of the dips switches. If the
switches are set without turning off the power source,
the contents of the setting are invalid.
RSW: Unit No. Setting
Setting is required. Set the unit No. of all indoor units
respectively and serially, by following setting position
shown in the table below. Numbering must start from "1" for
every indoor unit.
Main Unit
1 st. unit
4 th. unit
5 th. unit
8 th. unit
9 th. unit
12 th. unit
13 th. unit
DSW5
DSW8
Setting position
Set by inserting a
screwdriver into the
groove.
2 nd. unit
3 rd. unit
6 th. unit
7 th. unit
10 th. unit
11 th. unit
14 th. unit
15 th. unit
DSW3: Capacity Code Setting
No setting is required, due to setting before shipment. This
dip switch is utilized for setting the capacity code which
corresponds to the Horse Power of the indoor unit.
HP
0.8
ON
Setting Position
1 2 3 4
1.8
ON
Setting Position
1 2 3 4
2.8
ON
Setting Position
1 2 3 4
5
ON
Setting Position
1 2 3 4
DSW5: Refrigerant Cycle No. Setting
Setting is required. Setting position before shipment is all
OFF (Refrigerant cycle No. 0)
HP
0
ON
Setting Position
1 2 3 4
4
ON
Setting Position
1 2 3 4
8
ON
Setting Position
1 2 3 4
12
ON
Setting Position
1 2 3 4
DSW7: Fuse Recover
No setting is required, due to setting before shipment.
Setting position before shipment is all OFF.
In case of applying high voltage to the terminal
1,2 of TB2, the fuse (0.5) on the PCB1(M) is cut.
In such a case, firstly correct the wiring to TB2
and then turn ON #1 (as showing beside)
DSW8: (Not used)
No setting is required, due to setting before shipment.
Setting position before shipment is all OFF.
NOTE:
The mark " " indicates position of dips switches.
-
Figures show setting before shipment or after
selection.
1.0
1.3
1.5
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
2
2.3
2.5
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
3
3.5
4
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
6
ON
1 2 3 4
1
2
3
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
5
6
7
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
9
10
11
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
13
14
15
ON
ON
ON
1 2 3 4
1 2 3 4
1 2 3 4
ON
1 2

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis