Herunterladen Inhalt Inhalt Diese Seite drucken

Remote Controller Operation - Hitachi RCI-1.5FSN1E Installationsanleitung

Rci unit
Vorschau ausblenden Andere Handbücher für RCI-1.5FSN1E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 25

6. REMOTE CONTROLLER OPERATION

6.1. SETTING THE FILTER INDICATION INTERVAL
The FILTER interval indication on the remote control
Switch (PC-P1H) can be set a approximately 100, 1,200 or
2,500 hours (factory setting: 1,200 hours). If 100 or 2,500
hours is required, follow the instructions below.
Step 1: Changing to Optional Setting Mode
Press the CHECK switch and the RESET switch together
more than 3 seconds while the unit is stopped. The
operation mode is changed to the field setting mode,
"SERVICE" is indicated and "
indicated, press the
or
condition, press the CHECK switch and the mode is
changed to the optional setting mode.
Flickered (Press
Step 2: Selection of Indoor Unit for Optional
Setting
When the mode is changed to the optional setting mode,
the indication on the liquid crystal display is as shown
below.
The flickering indication of "
The address of the Indoor Unit for optional setting is
indicated.
The address of the refrigerant system for optional setting
is indicated.
Select the Indoor Unit to be set by pressing the
switch and indicate the address of the Indoor Unit. In this
condition, press the CHECK switch and the indication is
changed to the indication of optional setting:
6.2. SETTING OF HIGH SPEED TAP
The air flow volume can be changed according to the
ceiling height by setting the item code to "C5" form the
remote control switch (Refer to the Installation &
Maintenance Manual of the remote control switch for
details).
" flickers. When "
" is not
switch and set "
". In this
or
switch)
"stops.
or
REMOTE CONTROLLER OPERATION
NOTE:
In case that the both indications of the ADDS.
-
(Address) and RN. (Refrigerant Cycle Number) show
", the same setting is performed to all the indoor
"
units.
The indoor units not connected are not indicated.
-
Step 3: Optional Setting Items and Changing
Setting Conditions
The indication of optional setting is as shown below.
The code of optional setting is as shown below
The indications of ADDS. and RN. are turned OFF and
the optional setting condition is indicated.
The item code of optional setting is changed by pressing
the TIME
or
switch. The optional setting condition is
changed by pressing the CHECK switch. Set the item code
"
". In case of setting other indoor unit, press the
switch and the indication is changed to the condition of the
item "Step 2 Selection of Indoor Unit for Optional Setting".
The relation between the indication and the interval is
shown in the table below.
FILTER Indication Interval
Approx.
Approx. 100hr.
1,200hr.
b4 02
b4 01
B4 00 (*)
(*) Standard
Step 4: Cancelling Optional Setting Mode
Press the RESET switch in the condition of Step 2 or Step
3, the condition is changed to the standard condition.
NOTE:
The Label for checking the contents of the setting is
attached to the holding bracket. Write down the
contents of the setting on the label.
Ceiling Height
1.0 to 2.5HP
3.0 to 6.0HP
Below 2.7m
Below 3.2m
2.7 to 3.0m
3.2 to 3.6m
3.0 to 3.5m
3.6 to 4.2m
6
7
or
Approx.
No indication
2,500hr.
b4 03
b4 04
Setting of Remote
Control Switch
Standard
High Speed (1)
High Speed (2)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis