Herunterladen Diese Seite drucken

Swegon GOLD 11 Installationsanleitung Seite 14

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 15
11
2
4
1
3
25
27
29
26
28
30
GB
Term-inals
Function
1 and 2
Indication of heating demand
3 and 4
Indication of cooling demand
5 and 6
Group alarm A
7 and 8
Group alarm B
9 and 10
Cooling on/off, stage 1
11 and 12
Cooling on/off, stage 2
13 and 14
Power output heating/pump
15, 16 and 17
High-speed operation
indication
18, 19 and 20
In-operation indication
21, 22 and 23
Power output damper
25 and 26
External stop
27 and 28
External fire/smoke function
29 and 30
Stop/low speed switching
31 and 32
Stop/low speed – high speed
switching
33 and 34
External alarm input 1
35 and 36
External alarm input 2
37 and 38
Flow indication exhaust air
39 and 40
Flow indication supply air
41 and 42
Reference voltage
43 and 44
Continuously variable control
of cooling
45 and 46
External alarm reset
47 and 48
External set point
displacement
49 and 50
Input signal for exhaust air
fan, boosted flow/VAV control
51 and 52
Input signal for supply air fan,
boosted flow/VAV control
101 and 102
Control Voltage Output
103 and 104
Control Voltage Output
14
www.swegon.se
6
8
10
12
14
5
7
9
11
13
- + - +
31
33
35
37
39
32
34
36
38
40
Remark
Free contacts 5 A, 250 V. Closed when heat exchanger is operating and there is a heating demand.
Free contacts 5 A, 250 V. Closed when there is a cooling demand and when one of the cooling outputs
has an output signal.
Free contacts 5 A, 250 V. Closed when an alarm is initiated.
Free contacts 5 A, 250 V. Closed when an alarm is initiated.
Free contacts 5 A, 250 V. On/off control of the cooling unit. Activated from the hand-held terminal.
Free contacts 5 A, 250 V. On/off control of the cooling unit. Activated from the hand-held terminal.
Free contacts 5 A, 250 V.
Free closed contacts 5 A, 250 V.
Free switching contacts 5 A, 250 V.
230 V AC. 23 fixed phase, 21 controlled phase, 22 neutral.
Used to stop unit via normally closed contacts. Bridged when delivered. Terminals 25 and 26 are
connected during operation. If this connection is broken the unit will stop.
Used to stop unit via external fire or smoke detector. Bridged when delivered. Terminals 27 and 28 are
connected during operation. If this connection is broken the unit will stop and trigger the alarm.
External contact function. Switches timer between stop and low-speed operation.
External contact function. Switches timer between stop/low-speed and high-speed operation.
External contact function. External alarm can be obtained for GOLD.
External contact function. External alarm can be obtained for GOLD.
Output for EA flow indication, 0–10 V DC. Max. load 2 mA at 10 V DC.
Output for SA flow indication, 0–10 V DC. Max. load 2 mA at 10 V DC.
Output for constant 10 V DC. Max. load 10 mA.
Output for cooling 0–10 V DC. Max. load 2 mA at 10 V DC.
External closing contact function. Works in parallel with reset button on hand-held terminal.
Input 0–10 V DC. If supply air control is selected the supply air temperature set point will be offset. If
exhaust air control is selected the exhaust air temperature set point will be offset. Displacement ±5°C. If
ERS control is selected the EA/SA differential will be offset. The differential cannot be <0°C. The EA/SA
differential decreases as the input signal increases. Can be activated from the hand-held terminal.
Input 0–10 V DC. Controls exhaust air fan speed by means of boosted flow or VAV control.
Input 0–10 V DC. Controls supply air fan speed by means of boosted flow or VAV control.
Control Voltage 230 V AC. Max. load 1 A. Can be isolated by the safety switch.
Draws power across the power supply fuse.
Control Voltage 24 V AC. Max. load 16 VA. Can be isolated by the safety switch.
16
19
21
23
15
17
18
20
22
23
P N L
- + - +
- +
- +
- +
41
43
45
47
49
51
42
44
46
48
50
GOLDIN.11-15.050101
24
101 101 102 102
52
N
L
Reservation för ändringar.
103 103 104 104
GO G

Werbung

loading

Diese Anleitung auch für:

Gold 12Gold 15