4.2 Connection of Battery cables
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and
battery cables with sufficient cross section should be used. See table.
Recommended
2
cross section (mm
)
length up to 6 m
12/1600
Recommended
battery capacity
300 - 800
(Ah)
Remark: Internal resistance is the important factor when working with low capacity
batteries. Please consult your supplier or the relevant sections of our book "electricity on
board", downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Connect the battery cables: the + (red) and the - (black), to the battery see appendix A.
Reverse polarity connection (+ to – and – to +) will cause damage to the product. ()
Secure the nuts tightly in order to reduce the contact resistance as much as possible.
4.3 DC safety fuse
There is no safety fuse inside the inverter; this should be installed externally. The
recommended safety fuses can be found in the table below
12/1600
Recommended
DC fuse
12/1600
24/1600
50
25
24/1600
150 - 400
24/1600
300A
150A
48/1600
12/2000
25
70
48/1600
12/2000
75 - 200
350 - 1000 200 - 500
48/1600
12/2000
80A
350A
24/2000
48/2000
35
25
24/2000
48/2000
100 - 250
24/2000
48/2000
175A
100A