3.4 Protections and automatic restarts
Overload
Some loads like motors or pumps draw large inrush currents in a start-up situation. In
such circumstances, it is possible that the start-up current exceeds the over current trip
level of the inverter. In this case the output voltage will quickly decrease to limit the output
current of the inverter. If the over current trip level is continuously exceeded, the inverter
will shut down: wait 30 seconds and then restart.
After three restarts followed by another overload within 30 seconds of restarting, the inverter
will shutdown and remain off. The LEDs will signal shutdown due to overload. To restart the
inverter, switch it Off, then On.
Low battery voltage (adjustable)
The inverter will shut down when the DC input voltage drops below the low battery shutdown
level. After a minimum delay of 30 seconds, the inverter will restart if the voltages rise above
the low battery restart level.
After three restarts followed by a low battery shutdown within 30 seconds of restarting, the
inverter will shutdown and stop retrying. The LEDs will signal low battery shutdown. To restart
the inverter, switch it Off, and then On, or recharge the battery: as soon as the battery has
risen and then stays above the Charge detect level for 30 seconds, it will switch on.
See the Technical Data table for default low battery shutdown and restart levels. They can be
changed with the VictronConnect App.
High battery voltage
Reduce DC input voltage and/or check for a faulty battery- or solar-charger in the system.
After shutting down due to a high battery voltage, the inverter will first wait 30 seconds and
then retry operation as soon as the battery voltage has dropped to acceptable level. The
inverter will not stay off after multiple retries.
Definition
Solid on Overload
Low batt.
Slow
High batt.
Fast
High temp.
Double
High DC ripple
Fast
Red LED On or blinking
The inverter did shut down because of a protection. It will
no longer automatically restart. The red LED indicates the
reason for shutdown. Remove the cause and then restart
the inverter by switching it Off, and then back On.
Trouble shooting
Reduce load
Recharge or replace battery
Check DC cable connections
Check cable cross section as it may be insufficient.
See section 4.2 Protections and automatic restarts for
manual and automatic restart behavior.
Reduce DC input voltage, check for faulty charger
Reduce load and/or move inverter to better ventilated area
Check DC cable connections and cable cross section.