Components
n = Number of bytes in the process
image
m= Number of accesses in the process
*)
image
k= Number of consistency ranges in the
process image
B
In the expansion rack with local link
**)
Read byte/word/double word
Write byte/word/double word
C
In the expansion rack with remote link
**)
Read byte/word/double word
***)
Write byte/word/double word
D
In the DP area for the integrated DP
interface
Read byte/word/double word
Write byte/word/double word
E1 Consistent data in the process image for
the integrated DP interface
Read data
Write data
E2 Consistent data in the process image for
the external DP interface (CP 443-5
extended)
Read data
Write data
*)
The data of a module is updated with the minimum number of accesses.
(Example: There are 2 double word accesses for 8 bytes, for 16 bytes there are
4 double word accesses.)
**)
For I/Os which are plugged into the central rack or into the expansion rack, the specified
valule contains the runtime to the I/O module.
***)
Measured with IM460-3 and IM461-3 for a link length of 100 m
Execution Times of the SFC87 "C_DIAG"
The execution times of the SFC87 "C_DIAG" are missing in the current Instruction List on the
CPUs 412, 414, 416, 417. They are listed in the following table.
A5E00073168-07
CPU 414-4H / CPU 417-4H
CPU 414-4H
CPU 417-4H
solo
(m * 23 + n * 5) ms
(m * 28 + n * 5) ms
(m * 17 + n * 5) ms
(m * 20 + n * 5) ms
(m * 23 + n * 10) ms
(m * 28 + n * 10) ms
(m * 17 + n * 10) ms
(m * 20 + n * 10) ms
(m * 23 + n * 0.5) ms
(m * 28 + n * 0.5) ms
(m * 17 + n * 0.5) ms
(m * 20 + n * 0.5 ms
(k * 50 + n * 0.6) ms
(k * 100 + n * 1.2)ms
(k * 50 + n * 0.6) ms
(k * 100 + n * 0.6)ms
(k * 50 + n * 3.4) ms
(k * 100 + n * 4.0)ms
(k * 50 + n * 3.4) ms
(k * 100 + n * 3.4)ms