Herunterladen Inhalt Inhalt Diese Seite drucken

Chauvin Arnoux C.A 6545 Bedienungsanleitung Seite 55

Megohmmeter
Vorschau ausblenden Andere Handbücher für C.A 6545:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 65
Test voltage: ..................................... 1000 V
Insulation resistance (R): ......... 385 GOhm
DAR: .................................................... 1,234
PI: ........................................................ 2,345
DD: ...............................................................
Capacitance: .......................................... µF
I residual: ................................................ nA
Comments: ..................................................
.....................................................................
Date of next test : .......................... /..../.......
After a «Programmed time test» other results are printed (intermediate samples):
Time
Resistance
00 : 30
35.94 GOhm
01 : 00
42.00 GOhm
01 : 30
43.50 GOhm
etc.
6.3.2
Printing of memorised data (PRINT MEM key)
This is used to print the content of the unit's RAM.
The small display indicates 01: 01 for the OBJ number: TEST (print starting address).
The main display indicates the last recording in the memory (end print address).
For example 12: 06;
01 opposite the OBJ position flashes and the normal modification procedure must be used (
keys) to define the start/end of printing addresses.
To exit without printing, change the position of the rotary switch.
To start printing, press again on the PRINT key.
To stop printing, change the position of the rotary switch.
The printing of each data group is reduced to the main results.
Example:
CHAUVIN ARNOUX C.A 6547
Instrument number: 000 001
INSULATION RESISTANCE TEST
PURPOSE: 01
Description: ..................................................
.....................................................................
Date: .......................................... 31.03.1998
Starting time: .................................... 13h 35
Running time: ....................... 16 min 27 sec
Temperature: ................................. °C .... °F
Relative humidity: ..................................... %
Test voltage: ..................................... 5000 V
Insulation resistance (R): ............... 3.85 TΩ
DAR: ................................................... 1,273
PI: ....................................................... 2.382
DD: ...............................................................
Capacitance: ............................................ µF
I residual: ................................................ nA
Comments: ..................................................
Date of next test: ........................... /..../.......
Voltage
1005 V
1005 V
1005 V
A line for the signature of the operator appears at
the end of printing.
TEST: 01