ON delay of switching output.
(setting range 0...30 sec., default value = 0.00 sec.)
OFF delay of switching output.
(setting range 0...30 sec., default value = 0.00 sec.)
Setting POWER ON delay (switching output)
(setting range 0...30 sec., default value = 1.00 sec.) During this period, the switching
output does not react to events. This function is only of effect directly after switching on
the supply voltage.
Setting the wire-break detection time
(setting range 0.2...10.1 sec., default value = 10.1 sec.)
If no input signal is detected during this period, "No Input" appears on the display and
the outputs behave according to their settings
Setting the end value
(setting range 75...125 %, default value = 100 %)
Setting the zero point in relation to the previously set
output signal: (setting range -5...+5 mA / -2.5...+2.5 V;
default value = 0 mA / 0 V)
Setting the division factor from 0.1 to 9999 (default value = 1.0). Slow positioning tasks
require holed coupling halves with multiple divisions (factor > 1). Measuring the rotati-
onal speed of a motor at the gearbox requires a small division factor (factor < 1).
Setting the filter depth of the analog output when using frequencies as input value
(setting range 1...15).
This function can only be configured using the membrane keyboard.
Setting the analog output value if the measuring range is fallen below
(setting range 0.00...24.00 mA, or 0.00...12.00 V).
Setting the analog output value if the measuring range is exceeded
(setting range 0.00...24.00 mA, or 0.00...12.00 V).
Setting the analog output value with wire break or
an input signal that is not available
(setting range 0.00...24.00 mA, or 0.00...12.00 V).
Saving. By pressing the
parameters are saved.
By pressing the
key, the setting mode is interrupted without saving the parameters
set.
By pressing the
key, the current settings are overwritten by the default values. The
parameters of the frequency input and analog input are unaffected.
key, the set
19