Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze ELCAFHIxxx4E34NNPM Highline Montageanleitung Seite 84

Dezentraler frequenzumrichter, l-force drives
Vorschau ausblenden Andere Handbücher für ELCAFHIxxx4E34NNPM Highline:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4
Electrical installation
Communication
Baud rate / bus cable length
Baud rate [kbps]
9.6 − 93.75
187.5
500
1500
3000 − 12000
)
Note!
Ensure that the baud rate depending on the amount of data, cycle time and
number of stations is only selected as high as required for the application.
Specification of the transmission cable
Please follow the specifications of the PROFIBUS user organisation (PUO) for signal cables:
Bus cable specification
Specific resistance
Capacitance per unit length
Loop resistance
Core diameter
Core cross−section
Cores
84
Length [m]
1200
1000
400
200
100
135 − 165 W/km, (f = 3 − 20 MHz)
£ 30 nF/km
< 110 W/km
> 0.64 mm
2
> 0.34 mm
Double twisted, insulated and shielded
l
EDKLCFH1134−EPM DE/EN 1.0

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Lcu 5,5...11kw

Inhaltsverzeichnis