Grease separators Lipumax-P -B, -D, -DM, -DA
Installation
Ventilation line
Requirements:
Lay the ventilation line up to above the roof. Ventilate connection pipes longer than 5 m
separately.
If the inlet pipe above the grease separator has no separately ventilation connection
pipe over 10 m length, it must be equipped with an additional vent stack as close as
possible to the grease separator.
Instead of an additional connection in the inlet pipe near the grease separator, the
connection socket on the housing can be used.
Ventilation valves are not permitted in areas at risk of backflow or for ventilating the
grease separator.
Lay ventilation lines made of materials resistant to fatty acid (e.g. KML, PP, PE).
Connect on-site ventilation line DN 100/
Î
OD 110 mm to connection socket:
Smear the pipe spigot end and socket
seal with acid-free grease and push in the
pipe.
Connecting the supply pipe
Requirements:
Lay the supply pipe (empty pipe) from the plant room up to the housing (tank) with
gradient at least 1.5 – 2 %.
Do not use pipe bends with angles larger than 30°.
Insert the high-pressure hose (10, 20 or 30 m long) and connection cable of the HP
head (or qualitative pull wire) directly in the empty pipe.
Lay supply pipe made of materials resistant to fatty acid (e.g. KML, PP, PE).
Connect on-site supply pipe DN 100/
Î
OD 110 mm to connection socket:
Smear the pipe spigot end and socket
seal with acid-free grease and push in the
pipe.