Block until outdoor temperature >5°C
Wind alarm with wind > 4,0 m/s, for more than 1 s
Awnings:
Shade when sun intensity > 40 kLux
Shade upon sun from all directions ("Always")
and solar altitude between 0° and 90°
Block until indoor temperature >18°C
Block until outdoor temperature >5°C
Wind alarm with wind > 5,0 m/s, for more than 1 s
Night closure with twilight is deactivated
Closing at a certain time is deactivated
Automatic tilting/positioning system is deactivated
Shading delay upon sun, extend: 1 min,
retract: 12 min
Ventilators:
Ventilate when room air humidity > 80% RH
Ventilate if indoor temperature > 28°C
Winter mode when outdoor temperature < 1°C
Full use of gradation
No forced ventilation
With fresh-air/heating combinations on WGBL: heat when indoor temp. <
10°C, no night reduction
Air supply: winter mode when outdoor temperature < 1°C
With roof heaters with recirculation function: recirculate to gain heat and to
prevent water condensation are inactive
With WFL air supply units: summer mode active
Heating:
Heat if indoor temperature < 10°C
No night reduction
Air-conditioning:
Cool if indoor temperature > 30°C
With Daikin air-conditioning units: heat if indoor temperature < 10°C, no
night reduction, ventilate in automatic mode, do not ventilate when idle
Block ventilation for 120 min. after air-conditioning is switched off