Light replacement (see Fig. 8, page 11)
8.2.1 Remove the cover as described in 8.1.1 and 8.1.2
8.2.2 Both lights 7, 8 are now accessible and can be loosened. Only replace them by lights of the same
type (small bulb, GL 3.5 V 0.2 A-E10, DEHN Part No. 766 605).
8.2.3 Re-assemble in reverse order (do not remove screw and cover sealing).
8.2.4 Perform a functional test according to 5.1.
7 / 8
6
5
1 / 2
Fig. 8
9.

Maintenance test

The test interval for a PHE... voltage detector depends on its conditions of use, for example
frequency of use, environmental conditions and transport.
The test interval must not exceed 6 years. This also applies to PHE... voltage detectors which are
only stored in a warehouse!
Retain these instructions for use.