6. Commissioning, operation

6.4 Switching functions

Hysteresis function
GB
If the system pressure fluctuates around the set point, the hysteresis
keeps the switching status of the outputs stable. With increasing
system pressure, the output switches when reaching the switch point
(SP).
Contact normally open (HNO): active
Contact normally closed (HNC): inactive
With system pressure falling again, the output will not switch back
before the reset point (RP) is reached.
Contact normally open (HNO): inactive
Contact normally closed (HNC): active
Window function
The window function allows for the control of a defined range.
When the system pressure is between 'window high' (FH) and 'window
low' (FL), the output switches on.
Contact normally open (FNO): active
Contact normally closed (FNC): inactive
When the system pressure is outside 'window high' (FH) and 'window
low' (FL), the output does not switch on.
Contact normally open (FNO): inactive
Contact normally closed (FNC): active
20
WIKA operating instructions temperature switch model TSD-30
Fig.: Hysteresis function
Fig.: Window function