6. Gas exhaust conduction
Gas exhaust conduction position, see
point (K, L) in connection plan.
Gas units produce exhaust gas that
must be adequately vented through a
conducting system.
In order to avoid an inadmissible
concentration of health threatening
combustible product in the installation
area, the unit must be installed with
sufficient ventilation conditions (Room
air ventilation system with safety
switch)
Combi steamers can be connected as
follows:
Under an ventilation hood →
:
Picture 18
Unit type all sizes of appliance
Direct to the chimney→
under a ventilation ceiling→
Picture 19
Appliance with air baffle (optional)
When installing the unit on a
ventilation ceiling or a ventilation
hood, you must ensure that the safety
arrangements are maintained, that
the gas shuts off automatically when
the flue is not functioning.
When connecting unit type B13 direct
on a chimney, the gas exhaust
conduction ways must be cleaned
regularly. Observe the country codes
and regulations.
Gas exhaust pipes with sealed tight
connections.
The unit, that is the gas exhaust
conduction must be ensured against
movement or loosening of alignment.
The gas exhaust conduction must be
inspected by an authorized ventilation
specialist and installed in accordance
with district ventilation codes. It is
recommended that a written report of
the inspection be kept.
Exhaust temperature can be 300 -
400° C.
No flammable surfaces or materials in
the area. Fire protection regulations
must be adhered to!
Attention, inform the user of the
following:
,
The exhaust gas values are to be checked
when starting up.
: or
CO < 500 ppm
:
Erdgas
Liquid Propane gas
Liquid Butan gas
In the event of deviations from these
values, the appliance is to be adjusted..
46
The exhaust vents, their covering
(rear left) and the exhaust gas
itself can be of a very high
temperature. Exhaust gas and hot
steel parts can lead to burns.
The hand shower must only be
used for cleaning the inside of
the oven and not for the outer
casing! Do not spray the air inlets
and outlets and gas exhaust
openings.
Do not place any flammable
materials or objects on the unit.
Danger of burning.
8.6% ... 9.6% CO
10.0 ... 11.0 % CO
11.7 ... 12.7 % CO
EN
2
2
2