6.2.1 Connection version remote switch
The remote switch is directly connected to the emergency light electronics 6043/7.
The following connection versions are possible:
Point-to-point connection
6043/7..
x1
Linear connection
6043/7..
x2
6043/7..
x2
6043/7..
x2
6043/7..
x1
Remote switch
The following conductor specifications must be observed during connection.
maximum conductor length
maximum number of
light fittings
minimum cable
cross-section
226311 / 600960300010
2014-03-12·BA00·III·en·00
6043/7..
6043/7..
x1
x1
x1
Remote switch
x3
16401E00
Point-to-point connection
x 1
500 m
x 2
x 3
50
1.5 mm
6043/7..
16402E00
NOTICE
2
Emergency Light Fitting for Fluorescent Lamps
Series 6009
Engineering
Linear connection
100 m
50 m
500 m
30
2
1.5 mm