Conditions for trouble-free operation:
Except for the mains cable, use shielded cables only.
l
The shield must be carefully connected to PE.
l
Separate control and mains cables from motor cable!
l
Connect motor and mains PE conductors to separate PE terminals.
l
A
A
C
C
D
F
F
Abb. 1-16
0
Mains cable L1, L2, L3, PE
1
PE connection - mains cable
2
Use shielded motor cable (use low capacity motor cables)
3
EMC cable connection for motor cables
4
PE connection - motor cable
5
Shielded control cable
6
Shield connection for control cable (screw shield to shield sheet)
7
PE connection - terminal strip X2
8
Isolated terminal (e.g. star point for motor star connection)
9
Function module
X1
Terminal strip - mains connection
X2
Terminal strip - motor connection
PES
HF shield connection by connecting the shield with a surface as large as possible to PE
L

Wiring according to EMC requirements

X1
B
I
G
G
EDK82MV222 DE/EN/FR 3.0
Wall mounting
Shield connection
1. Prepare cable
X2
H
H
2. Route the cable through
I
I
J
3. Tighten the screw. The
8200mot100
3
the eyebolt of the shield
and bend the eyebolt.
shield must be tightly
connected to the shield
sheet.
0.7 Nm
6 lb-in
PES
17