The Centaur Charger must be installed in a dry, well-ventilated
area.
Too high an ambient temperature has the consequence of lower
output, shorter life or a complete shutdown of the Centaur
Charger.
The Centaur Charger is suitable for floor and wall mounting.
However, for optimum cooling, a vertical position is recommended.
The cables between the Centaur Charger and the battery must be
kept as short as possible to minimize cable losses. Input/output
connections refer to Figure 1.
Required tools and cables
• M6 Socket driver.
• Crosshead screwdriver no. 2 Phillips.
• Battery cables: minimum cable cross-section
Model
12/20
24/16
12/30
24/30
12/40
24/40
12/50
24/60
12/60
12/80
12/100
Length 0 - 6m
10mm²
AWG 7
16mm²
AWG 5
25mm²
AWG 3
35mm²
AWG 2
7