4 Assembly and connection

4.5 Performing the electrical installation

EN
4.5.1 Bus connection
(only in conjunction with several units
with a Comfort controller)
When using several cooling units, the serial device
interface X2 can be used to connect up to ten cool-
ing units with the bus cable (Model No. SK 3124.100).
Note:
The electrical signals at the X2 interface are
of an extra-low voltage (not extra-low safety
voltages in accordance with EN 60 335-1).
When interconnecting, please note the following:
– De-energise the cooling units to be connected.
– Ensure proper electrical insulation.
– Make sure the cables are not laid in parallel to
power lines.
– Make sure that the lines are short.
CS 9761.212, CS 9762.212
Fig. 6:
Electrical wiring plan no. 1
30
Mains
L2
X1
PE
L1
PE
1
N
6
1 2 3
1
L
N
S1 K2
Power
PE
A1
M1
1 2 3
C1
S
R
M1
C
F3

4.5.2 Installing the power supply

– Power supply is via the 9-pole female connector.
Complete the electrical installation by following the
wiring plan (see Fig. 6 and 7).
– If you would like the system messages from the
cooling unit to be evaluated via the system mes-
sage relay, you should also connect a suitable
low-voltage cable to connection clamps 3 – 5.
S1
2
3
4
5
11
X2
X3
K3
12
14
3
8
Hz
TB
K3
2
3
2
1
MS1
Serial
K1
NTC_I
Kx
NTC_E
NTC_C
NTC_A
Level
Term
2
M2
M4
F2
1
1 2 3
1 2 3
C4
C2
M
M
1~
1~
M2
M4
RITTAL outdoor cooling unit assembly and operating instructions
A2
2
B1
2
B2
2
B3
2
B4
2
B5
4
P
F2

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Cs 9762.212Cs 9768.152

Inhaltsverzeichnis