20
1 Troubleshooting
Code
Category
number
01
Indoor unit
Tripping of protection device
02
Outdoor unit
Tripping of protection device
Abnormality between indoor (or outdoor) and
03
outdoor (or indoor)
Transmission
04
Abnormality between inverter and control PCB
Voltage drop by excessively low or high voltage
06
Voltage drop
to outdoor unit
07
Decrease in discharge gas superheat
Cycle
08
Increase in discharge gas temperature
11
Inlet air thermistor
12
Outlet air thermistor
Sensor on
13
Freeze protection thermistor
indoor unit
14
Gas piping thermistor
19
Tripping of protection device for fan motor
20
Compressor thermistor
22
Outdoor air thermistor
24
Evaporating thermistor
Sensor on
outdoor unit
31
Incorrect setting of outdoor and indoor unit
35
Incorrect setting in indoor unit number
38
Abnormality of protective circuit in outdoor unit
Overload cooling
41
(Possibility of high pressure device activation)
Overload heating
42
(Possibility of high pressure device activation)
Pressure
Activation of low pressure decrease protection
47
device
48
Protection activation for overload operation
51
Abnormality of current sensor for inverter
53
Protection activation of transistor module
Inverter
54
Inverter fin temperature increase
55
Inverter abnormality
57
Outdoor fan
Fan motor abnormality
Indoor unit
b1
Incorrect unit number setting
number setting
EE
Compressor
Compressor protection alarm
41
PMML0248A
Content of abnormality
Leading cause
Failure of fan motor, drain discharge, PCB, relay, float switch activa-
ted
Activation of PSH, locked motor
Incorrect wiring, failure of PCB, tripping of fuse, power supply OFF
Failure in transmission between PCBs for inverter
Voltage drop of power supply. Incorrect wiring or insufficient capacity
of power supply wiring
Excessive refrigerant charge, expansion valve open lock
Insufficient refrigerant, refrigerant leakage, clogging or expansion
valve close lock
Failure of thermistor, sensor, connection
Failure of fan motor
Failure of thermistor, sensor, connection
Incorrect setting of capacity code
Duplication of indoor unit number
Failure of indoor unit PCB. Incorrect wiring connection to PCB in
indoor unit.
Outdoor unit pipe thermistor temperature is higher than 55ºC and the
compressor top temperature is higher than 95ºC when outdoor unit
protection device is activated
Indoor unit freeze protection thermistor temperature is higher than
55ºC and the compressor top temperature is higher than 95ºC when
outdoor unit protection device is activated
Stoppage by excessively decrease of evaporating temperature
(Te < -35ºC) is activated 3 times in one hour, locked motor in heating
operation
Excessive refrigerant. Pipe clogging. Compressor failure
Failure of control PCB
Inverter PCB abnormality.
Failure of compressor, clogging of heat exchanger
Abnormal inverter fin thermistor.
Clogging of heat exchanger
Abnormal outdoor fan
Failure of inverter PCB
Disconnected wire of incorrect wiring between control PCB and
inverter PCB.
Incorrect wiring or fan motor abnormality
Over 64 indoor units setting by number or indoor unit address
Failure of compressor.