16
1 Electrical wiring
16.3.2 Wire size
Connection wiring
Recommended minimum sizes for field provided wires:
Model
All Indoor Units
RAS-2HVNP
RAS-2.5HVNP
RAS-3HVNC
RAS-3HVRNS3
N O T E
Follow local codes and regulations when selecting field wires, Circuit breakers and Earth Leakage breakers
•
Use the wires which are not lighter than the ordinary polychloroprene sheathed flexible cord (code designation H05RN-F)
•
Main switch protection
Select the main switches in according to the next table:
All Indoor Units
ELB: Earth switch; CB: Circuit braker
IVX Premium and Standard series, and ES series
33
PMML0248A
Power supply
1~ 230V 50Hz
1~ 230V 50Hz
1~ 230V 50Hz
1~ 230V 50Hz
1~ 230V 50Hz
Model
Power supply
1~ 230V 50Hz
Outdoor unit
Power supply
RAS-2HVNP
1~ 230V 50Hz
RAS-2.5HVNP
1~ 230V 50Hz
RAS-3HVNC
1~ 230V 50Hz
RAS-3HVRNS3
1~ 230V 50Hz
Power source cable size
EN60 335-1
0.75 mm²
2.5 mm
2
4.0 mm
2
4.0 mm
2
4.0 mm
2
Max. current (A)
CB (A)
5.0
6
MC (A)
CB (A)
12.0
16
14.0
20
16.0
20
16.0
20
Transmitting cable size
EN60 335-1
0.75 mm²
ELB (no.poles/A/mA)
2/40/30
ELB
2/40/30