7.4
Filling the tanks with water
Prerequisite for fault-free filling is a make-up pressure at least 1.5 bar above the
final pressure "P
".
e
•
Without automatic make-up:
–
Use the draining valves or the system circuit to manually fill the vessel
to approximately 30 % of the vessel volume as a function of the system
temperature, 6.4 "Make-up and degassing variants", 24.
•
With automatic make-up:
–
The vessel is automatically filled to 12% of its volume, 6.4 "Make-up
and degassing variants", 24.
7.5
Starting Automatic mode
Automatic mode can be set after initial commissioning. Start automatic mode at the
control panel of the controller.
The following prerequisites must be met for automatic mode.
•
The device is filled with compressed air and water.
•
All required parameters are defined in the controller.
Press "Auto" for automatic mode on the control panel of the controller.
•
The "Auto" LED on the control panel illuminates to visually signal automatic
mode.
•
The actual values "Pressure (bar)" and "Filling level (%)" are shown in
alternation on the display.
– Possible errors are shown on the display.
Note!
Initial commissioning is completed and the device is in automatic mode.
8
Operation
8.1
Operating modes
8.1.1
Automatic mode
Use:
After initial commissioning has been successfully completed
Functions:
•
In automatic mode, the controller monitors the following functions:
–
Maintaining pressure
–
Expansion volume compensation
–
Automatically controlled make-up
•
The compressor and the "PV" valve (optional) are regulated by the controller
so that the pressure remains constant in a regulation range of ± 0.1 bar.
•
Faults are displayed on the control panel and in the app.
8.1.2
Stop mode
Use:
Stop mode interrupts automatic mode and is a prerequisite for manual mode.
Start:
Press "Stop" on the controller. The Auto LED of the control panel goes out. The
Stop LED lights up in yellow.
Functions:
Function monitoring is not performed in stop mode.
The following functions are deactivated:
•
The compressor is switched off.
•
The "PV" solenoid valve is closed.
Note!
If stop mode is activated for longer than 4 hours, an error message
appears on the device to signal an uncontrolled deactivation. This is also
indicated in the Reflex Control Smart app.
8.1.3
Use:
For testing and maintenance work
Start:
1.
2.
3.
4.
Switch the function on and off by touching the corresponding button:
•
Press the desired button:
•
Functions:
Manual mode allows you to select the following functions and to perform a test run:
•
•
•
•
9
9.1
Access to the Reflexomat RSC Smart is possible using Reflex Control Smart via a
Bluetooth-connected smartphone or tablet. The app is available from the app store
(Android or iOS), or via the QR code given below.
The Reflex Control Smart app provides the following functions amongst others:
•
•
•
•
•
•
Reflexomat RSC Smart — 08.01.2024-Rev. A
Manual mode
In the display, switch the system to stop mode.
In the app, switch the system to manual mode.
Setting Maintenance Manual mode
Start manual mode.
Select the desired function.
The button is highlighted white. The function is switched off.
The button is highlighted green. The function is switched on.
Compressor
Solenoid valve
Make-up
Potential free group fault.
Note!
The change in the filling level and the vessel pressure are indicated in
manual mode in the Reflex Control Smart app.
Controller
Reflex Control Smart
Intuitive and self-explanatory menu and operating guidance
Easy and quick commissioning (commissioning-wizard)
Querying of the system pressure
Individual configuration
Maintenance and troubleshooting wizard
Software updates for system control
Note!
Software updates for system control may only be executed via the app.
New available software updates are automatically displayed in the app.
Operation
English — 27