Herunterladen Diese Seite drucken

Interlogix DD1012AM Installation Sheet Seite 4

Vorschau ausblenden Andere Handbücher für DD1012AM:

Werbung

10
3
Alarm zone (2)
6
10
12
1
2
3
13
J1
JF JT JA
14
Single zone EOL
Zone state
Value
Tamper (short)
0 Ω
Normal
Rt
Alarm
Rt+Ra
Fault
Rt+Rf
AM*
Rt+Ra+Rf
Tamper (open)
*
SW2-4 must be set to On.
P/N 146551999-1 • REV C • ISS 30APR12
Ra
4
JA
Alarm (1)
JT
Rt
Tamper (3)
5
J1
Fault (4)
9
JF
Rf
4
5
6
7
8
9
SW1
SW2
Default
0 Ω
4.7 kΩ
9.4 kΩ
14.7 kΩ
19.4 kΩ
11
J1
JF
JT
SW1 - Generic settings
LED ON
Remote ON
Positive Polarity
Range
2
1
4
m
( 3 ft )
1
.
SW2 - AM/Fault settings
Mask to alarm and
fault relay
Auto reset
Advanced AM sens.
AM Day mode only
EN: Installation Sheet
Description
DD1012AM(-D) is a dual AM motion sensor.
It combines the patented PIR mirror optics technology with the
patented Range Controlled Radar technology.
Installation guidelines
See Figure 1.
The detector is intended to be mounted on walls but can also
be mounted on ceilings by using a mounting bracket.
Use the following guidelines to determine the best location to
install the detector.
Mount the detector so the expected movement of an
intruder is across the detection pattern (see Figure 3).
Mount the detector at a stable surface at a height between
1.8 m and 3.0 m (5.9 and 9.8 ft.) from the floor.
Do not mount the detector within 0.5 m (1 ft. 8 in.) of
metallic objects or within 1.5 m (4 ft. 11 in.) of fluorescent
lights.
Do not place objects in front of the detector that may
prevent a clear line of sight.
Place detectors at least 6 m (19 ft. 8 in.) apart, and use
the short-range setting to avoid interference, when
mounting detectors face to face.
The dual technology processing of this detector is very
resistant to false alarm hazards. However, avoid potential
causes of instability, such as:
PIR hazards:
Direct sunlight on the detector
Heat sources within the detector field of view
Strong air draughts onto the detector
Animals in the field of view
J1
On
=
3 resistor single
zone
(Terminal 3-10)
Off
Isolated fault
=
JA
contact
LED OFF
6
Remote OFF
5
Not used
4
Negative Polarity
3
2
2
2
2
1
1
1
1
12
m
6
m
9
m
(
40 .
ft )
(
20 .
ft )
(
30 .
ft )
Mask to fault relay
4
only
3
Authorized reset
2
Standard AM sens.
1
AM Day and Night
3 / 48

Werbung

loading

Diese Anleitung auch für:

Dd1012am-d