Informations for starting

Carry out following sight and performance checks for switching-on the smoke and heat vent control panel.
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
10k resistor
in smoke vent button
10k resistor
in fire detector
End module 2x47k
in junction box?
Connect mains.
battery lines. Control
Performance check alarm/reset and ventition
vent flap opens and
26/32
RZN 4402-K / RZN 4404-K
All cables
connected?
yes
yes
Factory-set?
(DIP switch)
yes
Ω
yes
Ω
yes
Ω
yes
Mains control
lightens?
yes
Connect
lightens?
yes
yes
Smoke
closes?
Partial or incomplete connection of
no
components can cause malfunction.
Check following connections: mains 230V,
drives, smoke vent buttons, when necessary
fire detectors and vent buttons. See wiring an
connection plans pages 23-25.
no
Delivery condition of DIP switch
see page 21.
Resistor must be cramped in electric last
button on terminal 3/8 (RT 45).
no
See connection plan pages 24.
Resistor must be cramped in last or only fire
detector on terminal 2 and 4
(type FO/FT).
no
Resistor remains in control panel between
terminal RM 1 and 2, when no fire detector is
connected.
See connection plan pages 25.
no
End module on last or only drive in junction
box on wire 5 orange, 6 black, 7 black.
See connection plan page 23.
no
Check line safety fuse in distribution box and
fuse mains in control panel.
Mains still not available or line switch
no
on " " or one of fuses faulty.
0
no
Possibly change poles in drive.
English
99.823.80 2.1/08/12