Encoding of line and group
1 = ON
OPEN-running time limitation
Using a potentiometer, running time in OPEN direction can be limited.
If the vent button is actuated in OPEN direction, the drive will run open
as long as the running time is set.
2 = ON
Ventilation time limitation
Using a potentiometer, ventilation tim can be set. Drives will automatically
close again, after the adjusted time has expired.
Only if DIP switch 5=ON
3 = ON
OPEN-retriggering (Only if DIP switch 1 = ON)
The OPEN-running time limitation can be retriggered again.
4 = ON
Power failure CLOSE
If the power supply breaks down, the drive will close.
5 = ON
Drives
CLOSE
5 = OFF
Drives are closing
vent button is
The function power failure-CLOSE will be ineffective (see DIP switch 4).
6 = ON
Drives
OPEN
6 = OFF
Drives will
7 = ON
In case of a
control panel will be switched on alarm, that means the
8 = ON
In case of a
control panel will be switched on alarm, that means the
DIP switch 8 must be on ON in conjunction with a ground in thermal maximal
detector (e.g. THE4).
9 = ON
Smoke detector alarm
the smoke vent button.
9 = OFF
Smoke detector alarm
10 = ON
SHEV retriggering on
intervals of 2 minutes according to VdS 2581.
99.823.80 2.1/08/12
O N
1
2
Factory default settings S1
up to final position by
only so long as
pressed
. OPEN-display on vent button is no longer possible then!
up to final position by
only OPEN as long as
line fault
(e.g. at an interrupted detector line or short circuit) the
group fault
(e.g. in case of an interrupted monitoring line) the
can not
will be
reset by pressing on the button
. The smoke vent is triggered for a duration of 30 minutes in
3
4
5
6
7
8
9 1
0
single pressing
the vent button or the button
single pressing
the vent button is
pressed
be reset by single pressing on the button
English
Only DIP switch 5 = ON
on vent button.
in the smoke
on vent button.
.
smoke vent opens
smoke vent opens
in the smoke vent button.
RZN 4402-K / RZN 4404-K
20
40
sec
60
2
15
30
min
45
2
.
.
in
21/32